产品分类

您的位置:首页 > 技术文章 > VLV铝芯电缆 VLV电力电缆运行敷设条件

技术文章

VLV铝芯电缆 VLV电力电缆运行敷设条件

时间: 浏览次数:339

VLV铝芯电缆 VLV电力电缆运行敷设条件

一、用途

本产品适用于交流50Hz,额定电压0.6/1KV线路中,供输配电能之用

二、使用特性
1)电缆导体的zui高额定温度为70℃。
2)短路时(zui长持续时间不超过5S)电缆导体的zui高温度不超过160℃。
3)敷设电缆时的环境温度不低于0℃,zui小弯曲半径应不小于电缆外径的10倍

三、型号、名称和使用范围

红旗集团供应VLV聚氯乙烯绝缘电线电缆 聚氯乙烯护套阻燃电力电缆

型号名称适用范围
VLV聚氯乙烯绝缘护套电力电缆敷设在室内、隧道及管道中、电缆不能承受压力和机械外力作用
ZR-VLV聚氯乙烯绝缘聚氯乙烯护套阻燃电力电缆敷设在室内、隧道及管道中、电缆不能承受压力和机械外力作用

 四、结构参数

0.6/1kv PVC绝缘PVC护套阻燃或非阻燃电力电缆

导线标称截面导体中单线根数绝缘厚度护套厚度电缆近似外径电缆近似重量20℃导体电阻≤(Ω/km)
Al20℃Al
mm2mmmmmmkg/kmΩ/km
1*2.510.81.46.547.912.1
1*411.01.47.463.07.41
1* 611.01.47.975.94.61
1*1071.01.49.293.03.02
1*1671.01.410.3132.21.91
1*2571.21.412.0185.41.20
1*3571.21.413.2228.70.868
1*50191.41.414.9289.80.641
1*70191.41.416.7374.20.443
1*95191.61.519.3501.40.320
1*120371.61.520.9590.30.253
1*150371.81.623.1721.30.206
1*185372.01.725.6891.60.164
1*240612.21.828.81114.00.125
1*300612.41.931.91396.00.100
1*400612.62.035.51742.00.0778
1*500612.82.139.72128.00.0605
1*630912.92.243.72605.00.0469
1*800612.92.446.13104.00.0367
2*1.510.81.810.5100 
2*2.510.81.811.311812.1
2*411.01.813.11607.41
2*611.01.814.11924.61
2*1071.01.816.72423.02
2*1671.01.818.83341.91
2*2571.21.822.24691.20
2*3571.21.824.55850.868
2*50191.41.821.86200.641
2*70191.41.924.77470.443
2*95191.62.029.29880.320
2*120191.62.131.311860.253
2*150371.82.234.714620.206
2*185372.02.437.916680.164
2*240612.22.444.321680.125
2*300612.42.549.026650.100
2*400612.62.856.033200.0778
3×1.510.81.8 10.9113 
3×2.510.81.8 11.813912.1
3×4111.8 13.71897.41
3×6111.8 14.82274.61
3×10711.8 17.62903.02
3×16711.8 19.94191.91
3×2571.21.8 23.65961.2
3×3571.21.8 23.17450.868
3×50191.41.8 26.58340.641
3×70191.42.0 28.810610.443
3×95191.62.1 33.614180.32
3×120191.62.2 37.117160.253
3×150371.82.3 41.921270.206
3×1853722.5 45.926020.164
3×240372.22.7 51.833080.125
3×300612.42.9 55.339790.1
3×400612.63.0 60.648690.0778
4×2.510.81.8 12.7 16912.1
4×4111.8 14.9 2217.41
4×6111.8 16.1 2714.61
4×10711.8 19.2 3883.02
4×16711.8 21.7 5091.91
4×2571.21.8 25.9 7221.2
4×3571.21.8 28.7 8990.868
4×50191.41.9 30.4 10910.641
4×70191.42.1 33.9 13980.443
4×95191.62.2 39.7 18660.32
4×120191.62.4 44.2 22650.253
4×150371.82.5 48.7 28110.206
4×1853722.7 53.5 34200.164
4×240372.22.9 55.4 43050.125
4×300612.43.0 61.0 53880.1
4×400612.63.2 70.0 67080.0778
5×2.510.81.813.6 19312.1
5×4111.816.1 2687.41
5×6111.817.1 3244.61
5×10711.821.0 4613.02
5×16711.823.8 6081.91
5×2571.21.828.7 8811.2
5×3571.21.932.0 11130.868
5×50191.42.137.4 15410.641
5×70191.42.241.7 19730.443
5×95191.62.448.1 26140.32
5×120191.62.553.0 31830.253
5×150371.82.758.6 35800.206
5×1853722.965.1 47670.164
5×240372.23.172.1 54610.125
5×300612.43.480.1 69640.1
5×400612.63.687.0 85640.0778


五、电缆运行敷设条件

电缆敷设
1、在敷设时电缆温度不低于0℃,环境温度不低于0℃时,应对电缆进行预热
2、敷设的弯曲半径不小于电缆外径的15倍
3、电缆敷设后,应经受以直流耐 压试验,时间15分试验电压3.5KV

在空气中敷设

1、单芯电缆平行敷设时中心距离:185mm2及以下电缆直径的2倍240mm2及以上为90mm
2、周围环境温度:30℃
3、导电线芯zui高允许温度:70℃。
4、不同环境温度下载流量的校正系数

环境温度20℃25℃35℃40℃45℃
校正系数1.121.060.940.870.79


直埋敷设
1、单芯电缆不接触敷设时,中心距离为电缆直径的2倍。
2、周围环境温度:25℃。
3、导电线芯zui高允许温度:70℃。
4土壤热阻系数:10℃m/w
5、不同环境温度下载流量校正系数

环境温度15℃20℃30℃35℃
校正系数1.111.050.940.88


短路容量

导电线芯短路时允许zui高温度zui高允许的短路电流
160℃I=94S/t A

传真:86-0316-5887669

邮箱:751339814@qq.com

地址:河北省廊坊市大城县刘演马工业区

版权所有 © 2020 天津市电缆总厂橡塑电缆厂销售科   备案号:冀ICP备16023464号-35  GoogleSitemap